Only the first 1024 bytes of the GSD file are displayed within the preview.
; Base GSD File for Eurotherm Process Automation T630 Process Controller
; General Information:
#Profibus_DP
Vendor_Name = "EUROTHERM Chessell"
Model_Name = "4100 Chart Recorder"
Revision = "1.1"
Ident_Number = 0x4100
Protocol_Ident = 0 ; PROFIBUS DP
Station_Type = 0 ; DP-slave
FMS_supp = 0
Hardware_Release = "V1.0"
Software_Release = "V1.0"
Redundancy = 0
Repeater_Ctrl_Sig =0
24V_Pins = 0
Implementation_Type = "ASIC_solution"
Slave_Family = 5 ; control group
Bitmap_Device = "EUR4100"
Bitmap_Diag = "EUR4100"
Bitmap_SF = "EUR4100"
;Supported Communication Speed:
Auto_Baud_supp = 1
9.6_supp = 1 ; Max length = 1200m (line type A or B)
19.2_supp = 1 ; Max length = 1200m (type A or B)
93.75_supp = 1 ; Max length = 1200m (type A or B)
187.5_supp = 1 ; Max length = 1000m (type A)
500_supp = 1 ; Max length =